INDU 30 controller
Industrial microprocessor devices
Controller INDU-30 , used in systems requiring control based on process time counting and regulation and control of parameters such as temperature and humidity.
It enables the use of various types of temperature measurement (digital sensors, current transducers, psychometric measurement) and humidity (current transducer, digital sensors) and equips the controller with two control inputs that can signal alarm states.
Destiny
Drying chambers Temperature and humidity control system Climatic chambers
Product features
INDU 30 controller
Product Features:
industrial structure with increased resistance to external conditions and mechanical damage
possibility of installation in "blind" holes (from the front)
very small installation depth
standard installation dimension 96×96 mm
click keys
clear LED displays
ready-made solution without the need to create firmware
Technical parameters
INDU 30 controller
General Information
Power
24V AC/DC Imax.140mA
110/230VAC Imax.30mA
Connectors
Physical parameters
Measurements
External 134x134x65mm (W x H x D)
Mounting 90x90mm (width x height)
Weight
Features
Level of security
IP 65 (front)
IP 20 (rear)
Temperature measuring range
Keyboard
Temperature measurement resolution
0,1℃ from -9,9℃ to 99,9℃
1℃ in other ranges
Humidity measuring range
Humidity measurement resolution
Communication
1xRS485 (PC)
1xRS485 (digital sensor)
Temperature measurement error
≤ ±0,5℃ (applies to the controller measurement path)
Humidity measurement error
EC conformity
2014/30 / EU
ROHS 2011/65/EU
2014/35 / EU
PN-EN IEC 61000-6-2:2019
PN-EN 61000-4-4:2013-05
PN-EN 61000-4-2:2011
PN-EN 61000-4-11:2007
PN-EN 61131-2: 2008
Register
Method of measuring humidity
Psychrometric measurement
Signal from the current transducer
Signal from digital sensor (RS485)
Signal from OneWire digital sensor
Inputs / outputs
Entrances
2 analog measurement configurable
(PT100/PT500/PT1000)
1 analog current (0mA÷20mA; 4mA÷20mA)
2 digital potential-free (control)
outputs
4 digital switching relays
(max load 250VAC/2A per channel)
1 digital relay contact
(max load 250VAC/2A)
Operating mode
Working conditions
Temperature: 0℃ ÷ 55℃
Humidity: 5%RH ÷ 85%RH
Installation data
Mounting
Screw-on 4 mounting holes (front)
or 4 mounting hooks (rear)