PARP

The MCC 026 microprocessor controller is used for the automatic control of industrial equipment requiring programmed operation and measurement of physical quantities, such as temperature, humidity, etc.

The controller is especially designed to control the technological process in DRYING CHAMBERS.

Intended use:
  • drying chambers
  • climatic chambers
  • temperature and humidity control systems

    Technical specifications

    POWER SUPPLY:

    • 24 VAC

    POWER CONSUMPTION:

    • 10 W

    DIMENSIONS:

    • Mounting hole dimensions: 143x238 mm
      Installation depth with connections: 48 mm
      External dimensions of the frame with seal: 187x280mm

    DISPLAY:

    • LED 0.8’’ x 4 digits LED 0.8’’ x 2 digits
    • LED 0.8’’ x 2 digits LED 0.8’’ x 2 digits
    • LED 0.8’’ x 2 digits LED 0.8’’ x 2 digits

    WEIGHT:

    • Controller: 1250 g
    • Transformer: 800 g

    ENCLOSURE:

    • Monolithic type Front Panel

    PROTECTION RATING:

    • From the connections’ side: IP 20
    • From the front: IP 65

    TEMPERATURE MEASUREMENT RANGE:

    • -30.. +400 °C (resolution 0.1 °C)

    HUMIDITY MEASUREMENT:

    • humidity control and setting 0-99%

    OPERATING CONDITIONS:

    • Operation temperature: 0 °C .. +60 °C
    • Storage temperature -20 °C .. +70 °C
    • Humidity: 0..75%

    PROGRAMS:

    • 50 (0..49) technological programs, editable by the user, automatic chamber washing program (99)

    DIGITAL COMMUNICATION:

    • 1x RS 485 - communication with a PC computer
    • 1x RS232

    TYPE OF REGULATING DEVICE:

    • No

    KEYBOARD:

    • 28 “CLICK SWITCH” keys

    MEASUREMENTS RECORDING

    • 2000 samples, logging set and measured values

    REAL TIME CLOCK

    • Yes

    PC SOFTWARE:

    • MPC3

    AUTOSTART

    • Yes, according to RTC with the functionality of programming the controller advance start, up to 24 hours

    INPUTS:

    • Analog inputs: 3
      Analog input type
      2x PT 100 temperature sensor (dry. wet)
      Temperature measurement range: -30.. 400°C
      Accuracy: 0.1 °C
      Humidity measurement range: 0..99 %
      Accuracy: 1%

      Current input 4..20 mA (humidity sensor)

    • Binary input: 1
    • BINARY INPUT TYPE:
      0-220 VAC (0-24 VAC)
    • Opto-isolation

    OUTPUTS:

    • Relay outputs: 8
      (Relay output type: Contact 250 V
      Total current of open relays: Iomax = 5 A)

    MISCELLANEOUS:

    • conditioned program execution, depending on humidity
    • software control of actuation equipment (contactors, solenoid valves, etc.)
    • manual operation mode

    Ask for this product
    Fill in the fields below and submit the form - we will reach you as soon as possible
    Contact data:
    Why you can trust our products?
    We continually develop new technologies

    We continually develop new technologies

    We are constantly developing our products and services in the field of industrial security systems. This practice gave us the position of the industry leader.

    We know your business needs

    We know your business needs

    We work with the best companies in the industry, delivering solutions that effectively meet the needs of transport monitoring.

    We bring long-term savings

    We bring long-term savings

    Advanced solutions for our digital recorders, detectors and controllers will help you optimize your operating costs.