What are you looking for?

Type to get immediate results, or press [ENTER] key for more details.

PARP
Intended use:
  • drying chambers
  • climatic chambers
  • temperature and humidity control systems

    Technical specifications

    POWER SUPPLY:

    • 230 VAC (optional: 24, 110)

    POWER CONSUMPTION:

    • 4.2 VA

    ACCURACY:

    • 0.1 °C

    DIMENSIONS:

    • Mounting hole dimensions: 93x93 mm
    • Installation depth with connections: 68 mm
    • External dimensions of the frame with seal: 144x144 mm

    DISPLAY:

    • LED ½’’ x 4 digits
    • LED ½’’ x 3 digits
    • LED ½’’ x 2 digits

    WEIGHT:

    • Controller: 600 g

    ENCLOSURE:

    • Monolithic type Front Panel

    PROTECTION RATING:

    • From the connections’ side: IP 20
    • From the front: IP 65

    TEMPERATURE MEASUREMENT RANGE:

    • -30.. +400 °C (resolution 0.1 °C)

    OPERATING CONDITIONS:

    • Operating temperature -10 °C .. +55 °C
    • Storage temperature -15 °C .. +60 °C

    DIGITAL COMMUNICATION:

    • 1 x RS-485 - communication with a PC computer
    • 1 x RS-485 digital temperature and humidity sensor

    TYPE OF REGULATING DEVICE:

    • 2 types of binary regulators and PID

    KEYBOARD:

    • 7 keys (micro switch)

    MEASUREMENTS RECORDING

    • Recording set and measured values – ca. 100,000 records.

    REAL TIME CLOCK:

    • Yes

    PC SOFTWARE:

    • Monitor INDU

    AUTOSTART

    • according to RTC with the functionality of programming the controller advance start, up to 10 days

    INPUTS:

    • 2 analog PT-100 (PT-500, PT1000) inputs
      channel1: temperature, “dry” thermometer
      channel3: temperature, “wet” thermometer
    • 1 analog input 0..20 (4..20) mA
      channel2: analog humidity sensor

    OUTPUTS:

    • 5 relay outputs

    MISCELLANEOUS:

    • conditional process termination, programmed from SETUP.

    RELAY CONTACT RATED LOAD

    • Recommended external protection - fuse: 6.3 A
    • Maximum total current (bus) -4A

      CAUTION! Using fuses over 6.3 A is not recommended

    COMPLIANCE WITH STANDARDS:

    • According to directives: 89/336/EEC as amended 
      91/263/EEC
      92/31/EEC
      93/68/EEC
    • PN-EN 60751 +A2:1997
    • PN-92 / E-08106
    • PN-EN 50082-2:1997
    • PN-EN 61000-4-5:1999
    • PN-EN 61000-4-4: 1999
    • PN-EN 61000-4-2: 1999
    • EN 61000-4-11: 1997
    • PN-EN 61000-4-8:1998
    • PN-EN 60584-1:1997
    • PN-89/M-53859

    Ask for this product
    Fill in the fields below and submit the form - we will reach you as soon as possible
    Contact data:
    Why you can trust our products?
    We continually develop new technologies

    We continually develop new technologies

    We are constantly developing our products and services in the field of industrial security systems. This practice gave us the position of the industry leader.

    We know your business needs

    We know your business needs

    We work with the best companies in the industry, delivering solutions that effectively meet the needs of transport monitoring.

    We bring long-term savings

    We bring long-term savings

    Advanced solutions for our digital recorders, detectors and controllers will help you optimize your operating costs.